20kV three phase transformer

  • product details
  • FAQ
  • Download

Features of Products

20kV Distribution Transformers The abbreviation "change"refers to a static electrical appliance in a power distribution system that converts AC voltage and current
according to the law of electromagnetic induction to transmit AC power. In some areas, power Transformers with a voltage level below 20 kV are called"distribution Transformers"or "
blending"for short. The installation of "matched"places and places is both a substation. Distribution Transformers should be installed on the column or open floor installation.

Standard

GB1094.1-2013; GB1094.2-2013; GB1094.3-2013; GB1094.5-2008; GB/T 6451-2008; GB/T 1094.10-2003; JB/T 10088-2004
IEC60076; SANS 780 STANDARDS

Features of Products

1. Meet or exceeds ANSI. IEC. GB. SANS. Standards
2. Safe Handling, Installation and Operation.
3. Attractive, modern appearance
4. Reasonable Structure
5. Fully-sealed
6. Higher system reliability
7. High security and reliability in operation
8. High capacity of overload and efficiency
9. Robust construction having excellent short circuit and thermal withstand capabilities
10. EVERPOWER Transformers are more efficient by Reduced no-load losses and Reduced load losses

Transformer normal service conditions

1.The height above the sea level is below 1000m;
2.Ambient temperature;
3.Highest air temperature+40℃;
4.Highest daily average air temperature+30℃;
5.Highest annual average air temperature+20℃;
6.Lowest outdoor air temperature-25℃;

S11-20kV distribution transformer technical data
Rated
Capacity
(kVA)
Voltage Group
(kV)
Vector
Group
Impedance voltage Loss(kW) No-load
current
Weight(kg) L*B*H(mm)
Outline dimension
Gauge vertical
horizontal
(mm)
High
Voltage
Low
Voltage
No-load Load Machine
weight
Oil
weight
Gross
weight
50       5.5 0.17 1.15 2.0 200 145 465 920*610*1000 450/380
100       0.23 1.92 1.8 330 165 635 920*680*1100 550/450
125       0.27 2.26 1.7 395 185 745 960*780*1120 550/470
160       0.29 2.69 1.6 505 205 885 1160*710*1180 550/520
200       0.34 3.16 1.5 580 225 995 1190*730*1190 550/520
250       0.41 3.76 1.4 695 245 1130 1280*820*1210 650/550
315 24 0.4 Yyno 0.49 4.53 1.4 745 260 1285 1380*910*1240 650/550
400 22 0.415 Dyn11 0.58 5.47 1.3 865 305 1500 1430*950*1320 650/550
500 20     0.69 6.58 1.2 985 335 1710 1520*1020*1360 750/600
630 19 0.433 Dyn5 0.83 7.87 1.1 1165 385 2010 1680*1150*1380 850/660
800       0.98 9.41 1.0 1335 415 2315 1810*1280*1430 850/660
1000       1.15 11.54 1.0 1655 515 2985 1840*1290*1540 850/660
1250       1.4 13.94 0.9 1890 630 3460 1850*1300*1730 850/660
1600       1.7 16.67 0.8 2220 710 4015 1920*1350*1790 850/700
2000       2.18 20.43 0.8 2530 730 4425 2020*1770*2040 820/820
2500       2.56 21.85 0.8 3165 795 5260 2080*1800*2130 1070/1070

 Note:Tapping range of high-voltage:±2*2.5%; Frequency:50Hz

 