Buy Main Transformer Factories – 220kV class three-phase on-load – JSM TRANSFORMER Detail:

220kV THREE-PHASE ON-LOAD VOLTAGE REGULATING

TRANSFORMER

Summary

220kV three-phase oil immersed on-load voltage regulating transformer brings about a series of major transformations in terms of material, technique, and construction. It is characteristic of compact construction,
low weight, high efficiency, low loss, low noise, and reliability of performance. The product can reduce considerable losses on grid and operational costs and extend distinct economic efficacy.
The product meets following national standards: GB1094.1-2013 Power transformers Part 1: General; GB1094.2-2013
Power transformers Part 2: Temperature rise; GB1094.3-2003 Power transformers Part 3: Insulation levels, dielectric tests and external clearances in air; GB1094.5-2003 Power transformers Part 5: Ability to withstand short-circuit;
GB/T6451-2015 Specification and technical requirements for three phase oil immerse power transformers.

图片1

Main 220kV level three-phase on-load voltage regulating power transformer technical parameters
Rated
Capacity
(kVA)
Voltage Combination Vector Gourp No-load Loss Load Loss No Load
Current
Short Circuit
Impedance
%
HV
(kV)
LV
k(V)
kW kW %
31500 6.3
6.6
10.5
11
YNd11 28 128 0.56 12-14
40000 32 149 0.56
50000 39 179 0.52
63000 46 209 0.52
75000 10.5
13.8
53 237 0.48
90000 64 273 0.44
120000 75 338 0.44
150000 220±2*2.5% 10.5,11,13.8 89 400 0.40
160000 242±2*2.5% 15.75 93 420 0.39
180000 18,20 102 459 0.36
240000 128 538 0.33
300000 13.8
15.75
18
21
154 641 0.30
360000 17 735 0.30
370000 176 750 0.30
400000 187 795 0.28
420000 193 824 0.28

Note 1Transformers with rated capacity less than 31500 kVA and other voltage combinations can also be provided as required.
Note 2 Transformers with low voltage of 35 kV or 38.5 kV can also be provided as required.
Note 3 The non-splitting structure is preferred. If there is any requirement for operation, sub-connectors can be set up.
Note 4 When the average annual load rate of transformer is between 45% and 50%, the maximum operating efficiency can be obtained by using the loss value in the table.

 

31500-300000kVA three-phase three -winding non-field excitation changing power transformer
Rated
Capacity
(kVA)
Voltage Combination Vector Group No-load loss
kW
Load loss
kW
No load current
%
Short-circuit impedance(%)
High Voltage
kV
Med-ium Voltage
(kV)
Low Voltage
(kV)
Step down Step down
31500 6.3,6.6
10.5,21
36,37
38.5
32 153.00 0.56
40000 38 183.00 0.5
50000 44 216.00 0.44
63000 52 257.00 0.44 H-M H-M
90000 220±2*2.5% 69 10.5,13.8
21,36,37
38.5
YNyn0d11 68 333.00 0.39 22-24 22-24
120000 230±2*2.5% 115 84 410 0.39 H-L H-L
150000 242±2*2.5% 121 100 487 0.33 12-14 12-14
180000 10.5,13.8
15.75,21
37,38.5
113 555 0.33 M-L M-L
240000 140 684 0.28 7-9 7-9
300000 166 807 0.24

Note 1: The capacity allocation of load loss in the table is (100/100/100)%. The capacity allocation of boost structure can be
(100/50/100)%. The capacity allocation of Buck structure can be (100/50/100)% or(100/50/100)%.
Note 2: Transformers with rated capacity less than 31500 KA and other voltage combinations can also be provided as required.
Note 3: Transformers with low voltage of 35 kV can also be provided as required.
Note 4: Priority should be given to non-splitting structure. If the operation requires, splitting can be set.
Note 5: When the average annual load rate of transformer is between 45%, the maximum operating efficiency can be obtained by using the loss value in the table.

 

31500kVA-180000kVA three-phase duplex-winding on-load tap changing power transformer
Rated
Capacity
(kVA)
Voltage Combination Vector Gourp No-load Loss Load Loss No Load
Current
Short Circuit
Impedance
%
HV
(kV)
LV
k(V)
kW kW %
31500 6.3,6.6
10.5,11,21
36,37
38.5
30 128 0.57 12-14
40000 36 149 0.57
50000 43 179 0.53
63000 50 209 0.53
90000 64 273 0.45
120000 220±8*1.25% 10.5,11,21
36,37
38.5
YNd11 79 338 0.45
150000 230±8*2.5% 92 400 0.41
180000 108 459 0.38
120000 81 337 0.45
150000 66
69
96 394 0.41
180000 112 451 0.38
240000 140 560 0.30

 

31500kVA-240000kVA three-phase three-winding on-load tap changing power transformer
Rated
Capacity
(kVA)
Voltage Combination No-load Loss Load Loss No Load
Current
Vector group Short Circuit
Impedance
%
Capacity
Assignment
HV
(kV)
Med-ium Voltage
(kV)
LV
k(V)
kW kW %
31500 6.3
6.6
10.5
11
21
33
36
37
38.5
35 153.00 0.63 H-M
12-14
H-L
22-24
M-L
7-9
100/100/100
100/50/100
100/100/50
40000 41 183.00 0.60
50000 48 216.00 0.60
63000 69 56 257.00 0.55
90000 220±8*1.25% 115 10.5
11
21
33
36
37
38.5
73 333.00 0.44 YNyn0d11
120000 230±8*1.25% 121 92 410 0.44
150000 108 487 0.39
180000 124 598 0.39
240000 154 741 0.35

Note 1The data listed in the table are applicable to depressurized structural products, and boost structural products can also be provided as required.
Note 2 Transformers with low voltage of 35 kV can also be provided as required.
Note 3 When the average annual load rate of transformer is between 45% and 50%, the maximum operating efficiency can be obtained by using the loss value in the table.

 

31500kVA-240000kVA three-phase three-winding on-load  self-coupled  power transformer
Rated
Capacity
(kVA)
Voltage Combination No-load Loss Load Loss No Load
Current
Vector group Short Circuit
Impedance
%
Capacity
Assignment
HV
(kV)
Med-ium Voltage
(kV)
LV
(kV)
kW kW %
31500 6.3
6.6
10.5
21
36
37
38.5
20.0 102 0.44 YNyn0d11 H-M
8-11
H-L
28-34
M-L
18-24
100/100/50
40000 24.0 125 0.44
50000 28.0 149 0.39
63000 33.0 179 0.39
90000 220±8*1.25% 115 40.0 234 0.33
120000 230±8*1.25% 121 10.5
21
36
37
38.5
51.0 292 0.33
150000 60.0 346 0.28
180000 68.0 398 0.28
240000 83.0 513 0.24

Note 1 The data listed in the table are applicable to depressurized structural products, and boost structural products can also be provided as required.
Note 2Transformers with low voltage of 35 kV can also be provided as required.
Note 3 When the average annual load rate of transformer is between 45% and 50%, the maximum operating efficiency can be obtained by using the loss value in the table.

 

31500kVA-240000kVA three-phase three-winding on-load  self-coupled  power transformer
Rated
Capacity
(kVA)
Voltage Combination No-load Loss Load Loss No Load
Current
Vector group Short Circuit
Impedance
%
Capacity
Assignment
HV
(kV)
Med-ium Voltage
(kV)
LV
(kV)
kW kW %
31500 6.3
6.6
10.5
21
36
37
38.5
20.0 102 0.44 YNyn0d11 H-M
8-11
H-L
28-34
M-L
18-24
100/100/50
40000 24.0 125 0.44
50000 28.0 149 0.39
63000 33.0 179 0.39
90000 220±8*1.25% 115 40.0 234 0.33
120000 230±8*1.25% 121 10.5
21
36
37
38.5
51.0 292 0.33
150000 60.0 346 0.28
180000 68.0 398 0.28
240000 83.0 513 0.24

1.Products exclusive in the product list may also be provided upon user requirements.Performance of the products will be customized.
2.Medium voltage device could select voltage value or tap other than those specified in the table upon user requirement.High voltage tapping may choose asymmetrical regulating tapping.
3.Short circuit impedance may choose value other than those defined in the table.
4.Final size is based on drawings of signed contract.

图片3


Product detail pictures:

Buy Main Transformer Factories –  220kV class three-phase on-load – JSM TRANSFORMER detail pictures

Buy Main Transformer Factories –  220kV class three-phase on-load – JSM TRANSFORMER detail pictures

Buy Main Transformer Factories –  220kV class three-phase on-load – JSM TRANSFORMER detail pictures

Buy Main Transformer Factories –  220kV class three-phase on-load – JSM TRANSFORMER detail pictures

Buy Main Transformer Factories –  220kV class three-phase on-load – JSM TRANSFORMER detail pictures


Related Product Guide:

We keep on with our enterprise spirit of "Quality, Efficiency, Innovation and Integrity". We intention to create extra worth for our buyers with our prosperous resources, superior machinery, experienced workers and superb services for Buy Main Transformer Factories – 220kV class three-phase on-load – JSM TRANSFORMER , The product will supply to all over the world, such as: Mexico, Casablanca, Detroit, We solution have passed through the national skilled certification and been well received in our key industry. Our specialist engineering team will often be ready to serve you for consultation and feedback. We've been able to also provide you with no cost samples to meet your needs. Best efforts are going to be produced to supply you the very best service and solutions. For anyone who is considering our business and solutions, please speak to us by sending us emails or get in touch with us right away. As a way to know our items and enterprise. lot more, you'll be able to come to our factory to find out it. We'll constantly welcome guests from around the globe to our firm. o build enterprise. elations with us. You should really feel absolutely free to make contact with us for small business and we believe we'll share the top trading practical experience with all our merchants.