Product Description:
The single-phase pole-mounted distribution transformers are specifically designed for the decentralization distribution network of servicing residential overhead
distribution loads of town and countryside.
They are also suitable for light and diversified power distribution systems.
Offers 2 basic transformer types and two kinds of metal core types conventional type and complete self protect type and for the transformer core.
Two types of materials are available:C.R.G.O wound core and amorphous metal core.
Standard
GB1094.1-2013;GB1094.2-2013;GB1094.3-2003;GB1094.5-2008;JB/T 10317-2002;IEEE Std C57.12.90-2010;ANSI C57.12.20;IEC60076;SANS780 STANDARDS.
Features of products
11kV single-phase column distribution transformer parameter table
11kV single phase pole-mounted distribution transformer | |||||||||||||
Rated Capacity (kVA) |
Voltage Group (kV) |
Vector Group |
Impedance voltage | Loss(kW) | No-load Current |
Weight(kg) | L*B*H(mm) Outline Dimension |
Gauge Vertical Horizontal (mm) |
|||||
High Voltage |
Low Voltage |
% | No-load | Load | % | Machine weight |
Oil weight |
Gross weight |
|||||
5 | 3.5 | 35 | 145 | 4 | 50 | 40 | 130 | 530*450*850 | 400/250 | ||||
10 | 55 | 260 | 3.5 | 65 | 40 | 150 | 560*450*870 | 400/300 | |||||
16 | 65 | 365 | 3.2 | 80 | 40 | 180 | 600*450*920 | 400/300 | |||||
20 | 11 | 80 | 430 | 3 | 100 | 50 | 205 | 620*450*940 | 400/300 | ||||
30 | 10.5 | 100 | 625 | 2.5 | 115 | 50 | 225 | 700*450*980 | 400/300 | ||||
40 | 10 | 0.22 | lio | 125 | 775 | 2.5 | 150 | 55 | 270 | 700*480*1040 | 400/300 | ||
50 | 6.3 | 0.24 | li6 | 150 | 950 | 2.3 | 175 | 70 | 310 | 650*510*1100 | 400/300 | ||
63 | 6 | 180 | 1135 | 2.1 | 190 | 80 | 340 | 660*520*1100 | 400/300 | ||||
80 | 200 | 1400 | 2.0 | 240 | 100 | 420 | 770*530*1120 | 450/300 | |||||
100 | 240 | 1656 | 1.9 | 295 | 100 | 490 | 840*600*1150 | 450/300 | |||||
125 | 285.00 | 1950 | 1.8 | 370 | 110 | 560 | 890*740*1160 | 500/400 | |||||
160 | 365 | 2365 | 1.7 | 430 | 130 | 650 | 950*790*1170 | 500/100 |
Single phase oil immersed pole-mounted transformer
Rating (kVA) |
HV(kV) | Tapping Range (%) |
LV(kV) | Loss(kwW) | Weight(kg) | ||||||||
No-load Loss |
Full Load Loss |
Oil Weight |
Total Weight |
||||||||||
15 | 33/1930/17.3213.2/7.6211/6.35 | ±2*2.5% or other |
0.03 | 0.195 | 45 | 294 | |||||||
25 | 0.05 | 0.4 | 68 | 362 | |||||||||
37.5 | 0.12 | 0.65 | 0.5 | 75 | 476 | ||||||||
50 | 0.24 | 0.8 | 0.6 | 93 | 553 | ||||||||
75 | 0.48 | 0.12 | 0.88 | 132 | 672 | ||||||||
100 | or | 0.21 | 1.12 | 141 | 742 | ||||||||
167 | 0.12-0.24 | 0.35 | 1.41 | 207 | 952 | ||||||||
250 | 0.24-0.48 | 0.5 | 2 | 375 | 1386 |